515Fault · Power sectionUsually repairable
SIMODRIVE 611U 515: Power Module Temperature Exceeded
What 515 means
The power module heatsink is too hot. The drive warns first and shuts down about 20 seconds later.
Symptoms
Trips after running a while under load, or in a hot cabinet.
Is it repairable?
Yes: fans are replaced and power modules repaired and tested.
Common causes
- Failed or clogged module fan
- Blocked airflow
- High cabinet temperature
- Too much load for the module size
Safe checks
- 1Check the fan and airflow through the module
- 2Clean dust
- 3Measure the cabinet temperature
Drives hold dangerous voltage after power-off. Checks should only be done by qualified personnel, with power isolated and the DC link discharged.
Reviewed by AutomIQ repair technicians. Code and name from the SIMODRIVE 611 universal Function Manual.
Related SIMODRIVE 611U faults
- 003NMI due to watchdog
- 006Checksum test error
- 020NMI due to cycle failure
- 028Actual current sensing during power-up
- 504Measuring circuit error, motor measuring system
- 505Measuring circuit error, motor measuring system absolute track